GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
266
For details about each index, please consult after-sale persons and technicians.
3.3 Cautions on Compressor Drive Replacement
1. Disconnect the power supply of the system. Set a multimeter to the AC voltage gear and measure
voltage between two of the lines (L1, L2, L3, and N). The measuring result should be 0 V
(sometimes, multimeters may be faulty and read false values). Set a mark beside the power
supply for warning.
2. Measure compressor drive DC bus voltage between two wire terminals of P, U, V, W and N. Set
the multimeter to the DC voltage gear and measure the voltage between P and N. The voltage
should be lower than 36 V. If no multimeter is available, wait for 20 minutes before performing the
steps below.
Note: The blue squares
indicate pads.
Содержание /E-X
Страница 27: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 23 Any nonconformity must be resolved through coordination...
Страница 233: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 229 Troubleshooting...
Страница 239: ...GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 235 Troubleshooting...
Страница 308: ...JF00303085...