GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
254
Note:
Before replacing the faulty compressors, make sure to block their openings with tapes. They
should be kept intact for further analysis.
Step 5: Check system parts.
If system oil is contaminated, check unit parts, including oil separator, gas/liquid separator, and
storage tank.
①
Check oil separator
Remove the oil separator. Tilt the separator to draw oil out into a container. Block the container for
further factory inspection.
②
Check oil balancer