GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
255
③
Check gas/liquid separator
After the gas separator is taken out, check whether it contains impurities. The check procedure is as
follows:
Use a glass container to hold the liquid. Check liquid impurities and colours and block the container
for further factory inspection.
Note:
If the compressor needs replacement, the gas/liquid separator needs replacement as well,
regardless whether the separator contains impurities or has faults or not.