GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
55
Branches of a manifold must be laid parallel and cannot be wrapped in superimposed mode.
F. T-type manifold can be laid in the following ways:
F1. T-type manifold must be installed horizontally with inclination.
Seal the branch
which are not used
gas side
liquid side
Seal the branch
which are not used
A view
B view
A view
B view
Inlet
Inlet
Outlet
Outlet
within ±15
°
within ±15
°
gas side
liquid side
A view
within
±10
°
within
±10
°
B view
gas side
liquid side
F2. The length of a straight pipe between T-type manifold pipe and Y-type manifold pipe cannot
be less than 500 mm.
F3. The length of a straight pipe between the T-type manifold pipe and the IDU cannot be less
than 500 mm.