![Gree /E-X Скачать руководство пользователя страница 184](http://html1.mh-extra.com/html/gree/e-x/e-x_service-manual_2260202184.webp)
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
180
2.2.4.61
“F5” Compressor 1 discharge temperature sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensors through temperature sensors circuit and judge the
range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
:
■Poor contact between discharge temperature sensor and terminal in mainboard interface
■Discharge temperature sensor is abnormal
■Detecting circuit is abnormal