![Gree /E-X Скачать руководство пользователя страница 199](http://html1.mh-extra.com/html/gree/e-x/e-x_service-manual_2260202199.webp)
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
195
Troubleshooting:
2.2.4.79
“H5” Inverter fan overcurrent protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H5 is displayed, it indicates
inverter fan overcurrent protection
Possible reason
:
■Poor contact of fan UVW wire
■Fan is broken
■Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal