Operation Using a Programmable Logic Controller (PLC)
Write
Write
Write Recipe
Recipe
Recipe
The Write Recipe command allows users to configure component selections of a recipe remotely. See
, for more details on recipes and recipe parameters. The return registers will echo the
arguments received.
NOTE:
NOTE:
NOTE: The recipe must be enabled via the ADM before it can be loaded for mixing.
Example: Configure Recipe 6 for
Component A = 2, Component B = 1, Component C = 2.
DCS
DCS
DCS Register
Register
Register
Parameter
Parameter
Parameter Description
Description
Description
Data
Data
Data
Type
Type
Type
Units
Units
Units
Value
Value
Value
Range
Range
Range
DCS
Command
Write Recipe
uint32
NONE
2
0 - 19
Argument 0
Recipe Number
uint32
NONE
6
0 - 40
Argument 1
Component A
uint32
NONE
2
0 – 30
Argument 2
Component B
uint32
NONE
31
0, 31 – 38
Argument 3
Component C
uint32
NONE
40
0, 39 - 46
Argument 4
Component D
uint32
NONE
N/A
0, 47 - 54
Acknowledge
Command Acknowledged
uint32
NONE
2 = ACK
0 - 4
Return 0
Recipe Number
uint32
NONE
6
0 - 40
Return 1
Component A
uint32
NONE
2
0 – 30
Return 2
Component B
uint32
NONE
31
0, 31 – 38
Return 3
Component C
uint32
NONE
40
0, 39 - 46
Return 4
Component D
uint32
NONE
N/A
0, 47 - 54
Return 5
Recipe Gun Assignment*
uint32
NONE
1
1 - 3
*
Only used when Multiple Guns is enabled.
Write
Write
Write Fluid
Fluid
Fluid Control
Control
Control Mode
Mode
Mode
The Write Fluid Control Mode command allows users to remotely change Fluid Control between ‘Flow’ and
‘Pressure’. See
, for more details on Fluid Control mode. The return registers will echo
the arguments received.
NOTE:
NOTE:
NOTE: The Fluid Control mode should be changed only when the system is in Standby or when the pumps are
powered off. Do not change Fluid Control modes during a mix operation.
Example: Change to Flow Control mode.
DCS
DCS
DCS Register
Register
Register
Parameter
Parameter
Parameter Description
Description
Description
Data
Data
Data
Type
Type
Type
Units
Units
Units
Value
Value
Value
Range
Range
Range
DCS
Command
Write Fluid Control Mode
uint32
NONE
3
0 - 19
0 = Flow
Argument 0
Fluid Control Mode
uint32
NONE
0 = Flow Mode
1 = Pressure
Acknowledge
Command Acknowledged
uint32
NONE
2 = ACK
0 - 4
0 = Flow
Return 0
Fluid Control Mode
uint32
NONE
0
1 = Pressure
3A6287E
49