MDE-3985L Encore® Installation Manual · May 2006
Page 79
Reference Information
Figure 4-5: Ultra Hi Shear Valve Installation
Follow shear valve manufacturers instructions for installation procedures, testing, and so on.
Install shear valve on each product inlet pipe.
Note: Encore dispensers require 1-1/2-inch male top shear valves. Gilbarco strongly
recommends using double poppet shear valves that shut off flow from both storage tanks and
internal to the unit. (examples: OPW #10BHMP or Exxon - OPW # 10RMSP) The Encore
Ultra-Hi dispensers use 2-inch male top shear valve. (example: Morrison Bros. 2-inch 636m)
For Ultra-Hi units install shear valve on each 2-inch inlet and outlet.
Install a shear valve on master dispenser satellite outlet and at satellite inlet.
Do not mount the shear valve upside down.
Be sure that the valve linkage is accessible and has no interference to open or close from
other piping, structure or components.
Note: The dispenser product inlet pipes need to be aligned with the shear valve.
Do not restrict shear valve linkage with pipes, braces, and so on.
Test shear valve operation.
Close shear valve until equipment start-up. Cap inlet pipe. This prevents dirt and other
particles from getting in product line. It also prevents fuel spillage.
Figure 4-6: Shear Valve
1-1/2
''
NPT Coupling on unit
Installing contractor supplied
black iron piping to coupling,
including union
Shear valve with shear point
installed flush with grade
±0.75 inch.
2
''
NPT Coupling on Ultra-Hi unit
Shear valve
Shear valve groove location must be
flush to island surface
± 0.25 inch
.
Shear groove
Island surface
Product inlet pipe