MDE-3985L Encore® Installation Manual · May 2006
Page 51
Installation
Mechanical and Hydraulic Related Items
Item
Procedure
See
Checked
MDE-4226
Related Item
1
Shear valves must be installed per valve manufacturer
recommendations. Shear point is
±
0.75 inch of grade and properly
mounted.
page 31
of this
manual
List 1, Item 1
2
The lower piping brace must be installed per the installation manual
and all product pipes properly anchored to it.
page 28
of this
manual
List 1, Item 13
3
Flexible pipe must not be used within the dispenser. However flexible
pipe meeting local and state codes can be used below the dispenser/
pump where allowed by regulatory authorities.
MDE-3802 Encore
and Eclipse Site
Preparation Manual
List 1, Item 2
4
Pumps (self contained units) must have a vacuum actuated pressure
regulating valve to prevent positive pressure at the pump base when
used with above ground tanks.
MDE-3802 Encore
and Eclipse Site
Preparation Manual
List 1, Item 3
5
Pumps require a check valve.
MDE-3802 Encore
and Eclipse Site
Preparation Manual
List 1, Item 4
6
Hose breakaways must be used and installed per manufacturer
recommendations. For units with retrievers, breakaways and whip
hoses must be attached to the nozzle end. For units without retrievers
it is attached to the dispenser end.
Manufacturers
specifications
List 1, Item 5
7
All hanging hardware must be checked for continuity.
page 46
of this
manual
List 1, Item 6
8
The unit must be properly anchored to the island.
page 31
of this
manual
List 1, Item 7
9
Vapor recovery piping at the dispenser/pump must have no traps or
sags.
page 32
of this
manual
List 1, Item 8
10
Verify correct nozzles, piping and brand panels for each grade.
unit order specific
List 1, Item 9
11
All code, regulatory agency or customer specified safety warning
signs, labels or decals have been installed.
as provided with and
for unit
List 1, Item 10
12
Long hose lengths beyond Gilbarco recommendations must not be
used without special retrievers.
For VaporVac hoses, no more than 6 of hose length may rest on
the ground when nozzle is resting in boot.
For Balance Vapor Recovery hoses, no portion of hose may be
on ground.
NFPA 30A
List 1, Item 11
13
Unit mounted using proper quantity, size, and strength mounting
hardware.
page 31
of this
manual
N/A