E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 25 of 34
Description
Function
To select as
output
proceed in chap-
ter
Output 1
Output 2
No output, device is
used as display unit
inactive
(contact is open)
inactive
(contact is open)
no
---
2-point-controller
switching function 1
(active = contact closed)
switching function 1
(active = contact is open)
2P
3- point-controller
switching function 1
(active = contact closed)
switching function 2
*1
(active = contact closed)
3P
2- point-controller with
min-/max-alarm
switching function 1
(active = contact closed)
min-/max-alarm
(alarm = contact closed)
2P.AL
min-/max-alarm,
common
min-/max-alarm
(alarm = contact is open)
min-/max-alarm
(alarm = contact closed)
AL.F1
min-/max-alarm,
individual
*2
max-alarm
(alarm = contact closed)
min-alarm
(alarm = contact closed)
AL.F2
*1
= Please take notice, that output 2 is a breaking contact of the relay, which means, that the con-
tact will be closed if the device have no power supply!
2
= Note:
please take notice, that output 1 and 2 has different contact types.
Through this the device will have different contact states by max- and min-alarm in
case of no power supply is present!
(Max alarm = contact is open, min alarm = contact is closed)
7.1 2-point-controller, 3-point-controller
This chapter describes how to configure the device as a 2-point-controller or 3-point-controller.
This instruction demands that you selected “
2P
“ or “
3P
“ as your desired output function like it is explained in
chapter
Fehler! Verweisquelle konnte nicht gefunden werden.
Fehler! Verweisquelle konnte nicht ge-
funden werden.
- Press button 1
(when not already done).
The device will be displaying “
1.on
“ (turn-on-point of output 1).
-
Use button 2 and button 3 to set the desired value, the device’s output 1 should be turning
on.
-
Press button 1 to validate your selection. The display shows “
1.on
“ again.
-
When pressing button 1 again, the device will be displaying “
1.off
“. (turn-off-point) of output
1)
- Use button 2 and button 3 to set the desired value,
the device’s output 1 should be turning
off.
-
Press button 1 to validate your selection. The display shows “
1.off
“again.
Example: You want to control the temperature of a heating coil, with a hysteresis of +2°C, to
120°C.
Therefore you will have to select the turn-on-
point “1.on“ to 120°C and the turn-off-
point to “122°C“.
When your heating coil temperature falls below 120°C it will be turned on. When
the temperature rises above 122°C the heating coil will be turned off.
Note: Depending on the inertia of your heating coil an overshooting of the temperature may be possible.
When selected ‘2-point-controller‘ you finished configuring your device. Press button 1 to switch over to
display the measuring value.
When selected ‘3-point-controller‘ please follow the instructions given below:
- Press button 1
(when not already done).
The device will be displaying “
2.on
“ (turn-on-point of
output 2).
1.ON
1.OFF
2.ON