E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 32 of 34
13 Specification
Absolute maximum ratings:
see chapter 5.2.
Measuring inputs:
Standard inputs for
Input type
Input signal
Measuring range
Resolution
Note
Standard
voltage-signal
0
– 10 V
0 ... 10 V
Ri > 300 kOhm
0
– 2 V
0 ... 2 V
Ri > 10 kOhm
0
– 1 V
0 ... 1 V
Ri > 10 kOhm
0
– 50 mV
0 ... 50 mV
Ri > 10 kOhm
Standard
current-Signal
4
– 20 mA
4 ... 20 mA
Ri = ~ 125 Ohm
0
– 20 mA
0 ... 20 mA
Ri = ~ 125 Ohm
RTD probes
Pt100 (0.1°C)
-50.0 ... +200.0 °C
(or -58.0 ... +392.0 °F)
0.1 °C / °F
3-wire-connection
max. perm. line resistance: 20 Ohm
Pt100 (1°C)
-200 ... +850 °C
(or -328 ... +1562 °F)
1 °C / °F
3-wire-connection
max. perm. line resistance: 20 Ohm
Pt1000 (0.1°C)
-100.0 ... +200.0
°C
(or -148.0 ... +392.0 °F)
0.1 °C / °F
2-wire-connection
Pt1000 (1°C)
-200 ... +850 °C
(or -328 ... +1562 °F)
1 °C / °F
2-wire-connection
Thermocouple
probes
NiCr-Ni
(type K) -270 ... +1350 °C
(or -454 ... +2462 °F)
1 °C / °F
Pt10Rh-Pt
(type S) -50 ... +1750 °C
(or -58 ... +3182 °F)
1 °C / °F
NiCrSi-NiSi
(type N) -270 ... +1300 °C
(or -454 ... +2372 °F)
1 °C / °F
Fe-CuNi (type J) -170 ... +950 °C
(or -274 ... +1742 °F)
1 °C / °F
Cu-CuNi (type T) -270 ... +400 °C
(or -454 ... +752 °F)
1 °C / °F
Frequency
TTL-Signal
0 Hz ... 10 kHz
0.001 Hz
signal low: 0.0
– 0.5 V
signal high: 2.7
– 24 V
Switching contact
NPN
0 Hz ... 3 kHz
0.001 Hz
an internal pull-up-resistor (~7 kOhm to
+3.3V) is connected automatically.
Switching contact
PNP
0 Hz ... 1 kHz
0.001 Hz
an internal pull-down-resistor (~7 kOhm
to +3.3V) is connected automatically.
Rotation
TTL-Signal,
Swit.contact NPN, PNP
0 ... 9999 U/min
0.001
U/min
Pre-scaling-factor (1-1000),
Pulse frequency:
max. 600000 p./min.
*
Up/Downwards
- Counter
TTL-Signal,
Swit.contact NPN, PNP
0 ... 9999
with pre-scaling factor: 9 999 000
Pre-scaling-factor (1-1000),
Pulse frequency:
max. 10000 p./sec. *
* = with switching contact accordingly to frequency input lower values may occur
Display range:
(voltage-, current and frequency-measurement)
-1999 ... 9999 digit,
initial value, terminal value and decimal point position arbitrary
Recommended rang: < 2000 digit
Accuracy:
(at nominal temperature)
Standard signal:
< 0.2% FS ±1 digit (from 0
– 50 mV: < 0.3% FS ±1 digit)
RTD
:
< 0.5% FS ±1 digit
Thermocouples:
< 0.3% FS ±1 digit (from type S: < 0.5% FS ±1 digit)
Frequency:
< 0.2% FS ±1 digit