11 Error codes
When detecting an operating state which is not permissible, the device will display an error code.
The following error codes are defined:
Err.1
Exceeding of measuring range
Indicates that the valid measuring range of the device has been exceeded.
Possible causes:
- Input signal to high.
- Sensor broken (Pt 100 and Pt 1000).
- Sensor shorted (0(4)-20 mA).
- Counter overflow
Remedies:
- The error-message will be reset if the input signal is within the limits.
- check sensor, transducer or transmitter.
- check device configuration (e.g. input signal)
- reset the counter.
Err.2
Values below measuring range
Indicates that the values are below the valid measuring range of the device.
Possible causes:
- Input signal is to low or negative.
- Current below 4mA.
- Sensor shorted (Pt 100 and Pt 1000).
- Sensor broken (4-20 mA).
- Counter underflow
Remedies:
- The error-message will be reset if the input signal is within the limits.
- Check sensor, transducer or transmitter.
- check device configuration (e.g. input signal)
- Reset the counter.
Err.3
Display range has been exceeded
Indicates that the valid display range (9999 digit) of the device has been exceeded.
Possible causes:
- Incorrect scale.
- Counter overflow
Remedies:
- The error-message will be reset if the display value is below 9999.
- Reset the counter.
- When happening frequently, check the scale-setting, maybe it was set
too high and should be reduced
Err.4
Values below display range
Indicates that display value is below the valid display range of the device (-1999 digit).
Possible causes:
- Incorrect scale.
- Counter underflow
Remedies:
- The error-message will be reset if the display value is above -1999.
- Reset the counter.
- When happening frequently, check the scale-setting, maybe it was set
too low and should be increased
Err.7
System error
The device features an integrated self-diagnostic-function which checks essential parts of the device
permanently. When detecting a failure, error-message Err.7 will be displayed.
Possible causes:
- Valid operating temperature range has been exceeded or is below
the valid temperature range.
- Device defective
Remedies:
- Stay within valid temperature range
- Exchange the defective device
Er.9
System error
The device features an integrated diagnostic-function for the connected sensor or transmitter.
When detecting a failure, error-message Err.9 will be displayed.
Possible causes:
- Sensor broken or sensor shorted (Pt 100 or Pt 1000).