E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 31 of 34
- Sensor broken (thermo-elements)
Remedies:
- Check sensor or exchange defective sensor
Er.11
Value could not be calculated
Indicates a measuring value, needed for calculation of the display value, is faulty or out of range.
Possible causes:
- Incorrect scale
Remedies:
- Check settings and input signal
12 Decommissioning, reshipment and disposal
12.1 Decommissioning
Always disconnect the device before from its supply before decommission (e.g. at fuse). Valid general
safety requirements shall be observed.
Please also make sure that connected Loads are disconnected also and are in a safe state.
12.2 Reshipment and disposal
All devices returned to the manufacturer have to be free of any residual of measuring
media and other hazardous substances.
Measuring residuals at housing or sensor may be a risk for persons or environment
Use an adequate transport package for reshipment, especially for fully functional de-
vices. Please make sure that the device is protected in the package by enough pack-
ing materials.
Add the completed reshipment form of the GHM website
http://www.ghm-messtechnik.de/downloads/ghm-formulare.html
.
The device must not be disposed in the unsorted municipal waste! Send the device
directly to us (sufficiently stamped), considering the above if it should be disposed.
We will dispose the device appropriate and environmentally sound