E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 6 of 34
2.2 Function
It is a universally applicable microprocessor controlled displaying, monitoring and controlling device.
The device is supporting one universal interface for the connection of:
- Standard transmitter signals (0-20 mA, 4-20 mA, 0-50 mV, 0-1 V, 0-2 V
and 0-10 V),
- RTD (Pt 100 and Pt 1000),
- Thermocouple probes (type K, J, N, T and S)
- Frequency (TTL and switching contact)
As well as rotation measuring, counting, etc...
Additionally two switching outputs, which can be configured as 2-point-controller, 3-point-controller, 2-point-
controller with min./max. alarm common or individual min./max. alarm. The state of the switching outputs is
displayed with 2 LED, whereby the LED (label 1) is displayed the state of the contact from relay 1 and the
LED (label 2) the state of the contact from relay 2.
(LED on = contact connected).
Furthermore both devices support one EASY Bus-interface for communicating with a host computer that
makes the device to a EASY Bus-module.
The device is being examined and completely calibrated.
Before the device can be used, it has to be configured for the customer’s application.
In order to avoid undefined input states and unwanted or wrong switching
processes, we suggest to connect
the device’s switching outputs after You
have configured the device properly.
By calling a configuration menu (configuration of the measuring input, con-
figuration of the analog output, configuration of the output function, offset-
and slope-adjustment) the measurement and regulation of the device will be
deactivated.
By leaving the menu the device will be reinitialised and the measur-
ing/regulation will be started again.
At the i
nput function “counter” the counter state will be reset by leaving the
menu.
3
Mounting in panels / housings
Panel cut-out:
Mounting: