E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 23 of 34
6.8 Interface mode
When the device is in the interface mode it won’t make any measurements by itself.
The value shown in the device’s display is sent via serial interface.
But the switching and alarm functions of the displayed value are still available.
The EASYBus-Address of the device needed for the communication can be set manually with the device
itself or with the help of an EASYBus-software (like EASYBus-Configurator).
Please note, when carrying out an EASYBus-system-
initialisation the device’s address will be reset auto-
matically.
This chapter describes how to configure the device as an EASYBus-display.
This instruction demands that you selected “
SEri
“ as your desired input type like it is explained in chapter
6.2.
The device has to display “
InP
“.
-
When pressing button 1 again, the device will display “
Adr
“ (address).
- Use button 2 and button 3 to select the desired address [0 ... 239] of the device.
-
Press button 1 to validate the selected device address. The display shows “
Adr
“ again.
You don’t need any further configuration but the outputs.
-
When pressing button 1 again, the device will be displaying “
outP
“ (output).
For configuring the outputs please follow the instructions given in chapter 6.9.
6.9 Selection of the output function
- After configuration of the input (chapter 6.3
– 6.8) you have to select the output function.
The display shows “
outP
“ (output).
-
Use button 2 and button 3 (middle or right button) to select the desired output-function
.
Description
Function
To select as
output
For switching
point setting
please
refer to chapter
Output 1
Output 2
No output, device is
used as display unit
inactive
(contact is open)
inactive
(contact is open)
no
--
2-point-controller
switching function 1
(active = contact closed)
switching function 1
(active = contact is open)
2P
3- point-controller
switching function 1
(active = contact closed)
switching function 2
*1
(active = contact closed)
3P
2- point-controller with
min-/max-alarm
switching function 1
(active = contact closed)
min-/max-alarm
(alarm = contact closed)
2P.AL
min-/max-alarm,
common
min-/max-alarm
(alarm = contact is open)
min-/max-alarm
(alarm = contact closed)
AL.F1
min-/max-alarm,
individual
*2
max-alarm
(alarm = contact closed)
min-alarm
(alarm = contact closed)
AL.F2
*1
= Please take notice, that output 2 is a breaking contact of the relay, which means, that the con-
tact will be closed if the device have no power supply!
2
=
Note: please take notice, that output 1 and 2 has different contact types.
Through this the device will have different contact states by max- and min-alarm in case of no power supply
is present!
(Max alarm = contact is open, min alarm = contact is closed)
.
Depending on your output function setting, it may be possible that one or more settings described below
won’t be available.
-
When pressing button 1 again, the device will display “
1.dEL
“ (delay of output 1).
ADR
OVTP
1.DEL