56
NRG 26-61 - Installation & Operating Manual -
819874-00
System malfunctions
Checking installation and function
When you have remedied system malfunctions, perform a function test as follows.
■
■
Check the limiter functions by bringing the level below the set low water (LW) and above the set high
water (HW) limits. In this case, the equipment must behave as if there were an alarm.
■
■
Check the switchpoint when bringing into service and every time the NRG 26-61 level electrode
is replaced.
System malfunctions in the NRG 26-61 level electrode also trigger a system malfunction in the
URS 60 / URS 61 safety control unit. The output contacts open without a delay and the relevant
signal output is activated.
If you require assistance, please tell us the indicated fault code.
In the event of malfunctions or faults that cannot be remedied with the aid of this Installation &
Operating Manual, please contact our service centre or authorised agent in your country.