NRG 26-61 - Installation & Operating Manual -
819874-00
Behaviour in the event of a low-level alarm (LW)
The level electrode is
immersed only
to below the low-level mark
(LW)
The level is below the AL.Lo
alarm limit
Display:
LO.LE and e.g. 009.5
alternating
The alarm message (Low Level) and the current
reading are shown alternately on the display
LED 1
:
Alarm LED lights up red
The MIN alarm is active
LED 2:
Operating LED is OFF
Alarm
Behaviour in the event of a high-level alarm (HW)
The level electrode is
immersed to above the
high-level mark (LW)
The level is above the AL.Hi
alarm limit
Display:
HI.LE and e.g. 092.5 alternating
The alarm message (High Level) and the current
reading are shown alternately on the display
LED 1
:
Alarm LED lights up red
The MAX alarm is active
LED 2:
Operating LED is OFF
Alarm
■
■
The alarm state is transferred to the URS 60 / URS 61 safety control unit via CAN data telegram.
■
■
There, once the time delay has elapsed, the alarm message triggers the safety shutoff.
■
■
The affected signal output is activated.
■
■
The URS 60 / URS 61 safety control unit does not automatically lock the safety contacts.
Behaviour in the event of a malfunction (fault code display)
On the occurrence of a fault
Display:
e.g. E.005
LED 1
:
Alarm LED lights up red
A fault code is permanently displayed,
fault codes see page 52
There is an active fault
LED 2:
Operating LED is OFF
A fault is present
■
■
The fault or error state is transferred to the URS 60 / URS 61 safety control unit via CAN data telegram.
■
■
The fault causes this unit to execute an undelayed safety shutoff.
■
■
The affected signal output is activated.
■
■
The URS 60 / URS 61 safety control unit does not automatically lock the safety contacts.
Electrode alarms and faults cannot be acknowledged.
When the alarm or fault is cancelled the display also goes blank, and the URS 60 / URS 61
safety control unit closes the safety contacts and deactivates the relevant signal outputs once
more.
Starting, operation and testing