34
NRG 26-61 - Installation & Operating Manual -
819874-00
Installation examples with dimensions
Key Fig. 11 to Fig. 15
1
Fig. 11, 12:
Flange (PN 40, DN 50) DIN EN 1029-01 (single electrode)
Fig. 14:
Flange (PN 40, ≥ DN 80) DIN EN 1029-01 (single electrode)
Fig. 13, 15:
Flange (PN 40, DN 100) DIN EN 1029-01 (electrode combination)
2
Standpipe in connecting flange (perform preliminary inspection of standpipe during boiler inspection)
3
Pressure relief hole
Ø
20 mm
4
Highest possible HW mark
5
Electrode rod
6
Protective tube DN 80 (in France as per AFAQ ≥ DN 100)
7
Protective tube DN 100
8
Distance between electrode rod and protective tube ≥ 14 mm
9
Minimum dimension (x) = 10 mm below the electrode length (electrode length, see page 19)
0
Lowest possible LW mark (upper bound)
!
Reducer DIN 2616-2, K-88.9 x 3.2 - 42.4 x 2.6 W
"
Reducer DIN 2616-2, K-114.3 x 3.6 - 48.3 x 2.9 W
§
Level pot ≥ DN 80
$
Centre distance of standpipe
%
Additional electrode
Aligning the terminal box
If necessary, you can orientate the display in the desired direction by rotating the terminal box.
ATTENTION
Rotating the terminal box ≥ 180° will damage the level electrode’s internal wiring.
■
■
Never rotate the terminal box more than 180 degrees in either direction.