52
NRG 26-61 - Installation & Operating Manual -
819874-00
System malfunctions
Indication of system malfunctions using fault codes
Fig. 20
Fault code display
Fault code
Internal
designation
Possible faults
Remedy
E.001
MinCh1Err
Channel 1 reading below
minimum, possible internal open
circuit
Is the level electrode no longer immersed?
Check the installation location, replace the
level electrode if necessary
E.002
MinCh2Err
Channel 2 reading below
minimum, possible internal open
circuit
Is the level electrode no longer immersed?
Check the installation location, replace the
level electrode if necessary
E.003
MaxCh2Err
Channel 2 reading above
maximum, possible internal open
circuit
Replace the level electrode
E.004
Ch1Ch2DiffErr
Difference between channels 1
and 2 exceeds 10 % error toler-
ance, internal short circuit
Replace the level electrode
E.005
MaxCh1Err
Channel 1 reading above
maximum, possible internal open
circuit
Replace the level electrode
E.006
MinTSTCh1Err
Channel 1 reading internal
capacitance (47pF)
Replace the level electrode
E.007
MaxTSTCh1Err
Channel 1 reading reference
capacitance (1nF || 47pF)
Replace the level electrode
E.008
MinTSTCh2Err
Channel 2 reading internal
capacitance (47pF)
Replace the level electrode
E.009
MaxTSTCh2Err
Channel 2 reading reference
capacitance (1nF || 47pF)
Replace the level electrode
E.010
PWMTSTCh1Err
Channel 1 reading with disabled
measurement signal
Replace the level electrode
E.011
PWMTSTCh2Err
Channel 2 reading with disabled
measurement signal
Replace the level electrode
OK
!
+
-
1
1
Actual value display/fault code/limit value, green, 4 digits