Connecting the CAN bus system
Bus line, cable length and cross-section
■
■
Use a shielded, multi-core, twisted-pair control cable, e.g. UNITRONIC
®
BUS CAN 2 x 2 x .. mm
2
or RE-
2YCYV-fl 2 x 2 x .. mm
2
as the bus line.
■
■
Pre-wired control cables (with plug and coupling) are available as accessories in various lengths.
■
■
The baud rate (transfer rate) is determined by the cable length between the bus terminal devices, and
the wire cross-section is determined by the overall power input of the measuring sensors.
■
■
0.2 A at 24 V is required per sensor. With five sensors, there is therefore a voltage drop of approx. 8 V
per 100 m when using cables of 0.5 mm². In this case, the system is operating at its limits.
■
■
With five or more sensors and a cable length of ≥ 100 m, the wire cross-section needs to be doubled
to 1.0 mm².
■
■
At larger distances of > 100 m, the 24 V DC supply can also be connected on site.