40
NRG 26-61 - Installation & Operating Manual -
819874-00
Bringing into service
Key to parameters:
■
■
099.9 = actual value display, the current measured level based on the 0 - 100 % calibration
■
■
Id.Lo = limiter ID; for the LW limiter function *
■
■
Id.Hi = limiter ID; for the HW limiter function *
* Effect on the URS 6x safety control unit
■
■
GrP
= controller group (effect on URB 60 / SPECTOR
control)
■
■
bd.rt = baud rate
■
■
°C.in = display ambient temperature of housing
■
■
AL.Lo = sets the LW alarm limit for the limiter function
■
■
AL.Hi = sets the HW alarm limit for the limiter function
■
■
CAL.L = lower bound calibration to 0 %
■
■
CAL.P = calibrates measuring range to an intermediate value above 25 % (alternative to CAL.H)
■
■
CAL.H = upper bound calibration to 100 %
■
■
Filt
= filter constant
■
■
diSP = initiate a display test
■
■
ConP = activation of compatibility mode; for operation with SPECTORconnect, do not
change setting (ConP = oFF)
Notes on changing communication parameters “bd.rt, Id.Lo; Id.Hi or GrP”
All CAN bus equipment from GESTRA AG has default ex works parameter settings, which
enable a standard system to be brought into operation without making any changes.
Please follow the steps below if you need to make changes to communication
parameters:
■
■
Set the same baud rate for all bus nodes.
■
■
To apply changed communication parameters, perform the steps below on the URB 60
visual display and operating unit or the SPECTOR
control:
■
◆
Device list - Reimport
To do this, please read the instructions in the Installation & Operating Manual of the
URB 60 visual display and operating unit or the SPECTOR
control.