NRG 26-61 - Installation & Operating Manual -
819874-00
Relationship between display and LEDs and the operating state of the level electrode:
Start
Switch on
supply voltage
All LEDs light up - Test
Display:
S-xx = software version
t-07 = equipment type NRG
26-61
The system is started and tested.
The LEDs and display are tested.
Bringing into service for the first time
Switch on
supply voltage
Display:
LO.LE + HI.LE alternating
LED 1:
Alarm LED lights up red
LED 2:
Operating LED is off
Low and high-level alarm (LW and HW) based on
factory-set alarm limits “
AL.Lo
” and “
AL.Hi
”.
First, set the alarm limits to suitable values for your
specific plant, see page 42.
Normal operation
The level electrode
is immersed within the set
measuring range
Display:
e.g. 047.3
LED 2
:
Operating LED lights up green
Displays the current level as % of the calibrated
measuring range.
See the following pages for more information and tables.
Starting, operation and testing