NRG 26-61 - Installation & Operating Manual -
819874-00
Bringing into service
Changing the “Id.Lo / Id.Hi” limiter ID
To set the limiter ID, please also read the instructions in the Installation & Operating Manual of
the URS 60 / URS 61 safety control unit.
Pay attention to the setting instructions on page 39 and proceed as follows:
1.
Select the parameter “
Id.Lo or Id.Hi
”.
Id.Lo
= limiter ID for the 2nd low water electrode
Id.Hi
= limiter ID for the 1st high water electrode
2.
Press and hold the rotary knob until the current limiter ID flashes on the display.
3.
Set the desired ID (off/0001 to 0008).
off = the NRG 26-61 level electrode has no effect on the URS 60 / URS 61 safety control unit.
4.
Save your setting by pressing the rotary knob for approx. 1 second.
Changing the controller group “GrP”
For setting the controller group, please also pay attention to the information in the Installation
& Operating Manual of the NRR 2-60 or NRR 2-61 level controller.
Pay attention to the setting instructions on page 39 and proceed as follows:
1.
Select the parameter “
GrP
”.
2.
Press and hold the rotary knob until the current controller group ID flashes on the display.
3.
Set the desired controller group (1 to 4).
4.
Save your setting by pressing the rotary knob for approx. 1 second.
Changing the baud rate “bd.rt”
You must set the same baud rate for all bus nodes.
Pay attention to the setting instructions on page 39 and proceed as follows:
1.
Select the parameter “
bd.rt
”.
2.
Press and hold the rotary knob until the current baud rate flashes on the display.
3.
Set the desired baud rate (50 kBit/s or 250 kBit/s).
4.
Save your setting by pressing the rotary knob for approx. 1 second.