System malfunctions
Common faults during use
Immersion of the level electrode is not detected (“o.P.E.r.” is not displayed)
Possible causes if no fault indications are present
Remedy
There may be no supply voltage.
■
■
Switch on the supply voltage.
■
■
Check that the wiring conforms to the
wiring diagrams.
The electrode body has no earth connection to the
tank.
■
■
Check and clean sealing surfaces.
■
■
Always use the supplied metal sealing ring, see page
4.
■
■
Make sure the thread of the measuring electrode does
not have insulating material wound around it, e.g. hemp
or PTFE tape.
The inner seal of electrode rod is damaged.
Replace the level electrode.
The ambient temperature may be too high,
> 75 °C.
■
■
Check installation location
■
■
Lower the ambient temperature
of the terminal box.
Non-immersion of the level electrode is not detected (“LO.LE.” is not displayed)
Possible causes if no fault indications are present
Remedy
The vent hole in the protective tube is missing, clogged
or flooded.
■
■
Check the protective tube.
■
■
Drill a vent hole in the protective tube.
The shut-off valves of the external measuring cylinder
(optional) may be closed.
Open the shut-off valves.
The electrode extension is in contact with earth.
Check the installation location of the level
electrode and change if necessary.