NRG 1x-60 - Installation & Operating Manual -
819681-00
Bringing into service
Checking the low water switchpoint by lowering the level
Incorrectly installed, shortened or bent level electrodes result in a loss of function that
can jeopardise system safety.
■
■
Check the low water switchpoint when bringing into service and every time the NRG 1x-60
level electrode is replaced.
■
■
Never start up any system without first checking that low water switchpoints are correct.
■
■
NRG 1x-60 level electrodes may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
Checking the limiter switchpoints by initiating a test function
Check the low water (LW) switchpoint by letting the water drop below the defined limit. In this case, the
equipment must behave as if there were an alarm, see page 46, “Test” table.
Lockout function
If the installation requires a lockout function, this must be implemented in the downstream
(safety) circuit. This circuit must conform to the requirements of EN 50156.