NRG 1x-60 - Installation & Operating Manual -
819681-00
Test
Checking the safety function by simulating the alarm state
In operating mode:
Press the rotary knob on the
NRG 1x-60 and hold until the
end of the test
or
press button 1, 2, 3 or 4 of the
URS 60 / URS 61 safety control
unit and hold until the end of
the test
or
open the relevant menu on the
URB 60 and initiate the test
function.
Display:
LO.LE
The system simulates a level electrode that is no
longer immersed.
LED 1
:
Alarm LED lights up red
Low-level alarm
LED 2:
Operating LED is OFF
Alarm
■
■
The switch-off delay is running, the signal output closes with/without
a delay.
■
■
The time delay has elapsed, the output contacts open, the signal
outputs close.
■
■
The test ends.
Faulty equipment jeopardises system safety.
■
■
If the level electrode does not behave as described above, it may be faulty.
■
■
Perform failure analysis.
■
■
NRG 1x-60 level electrodes may only be repaired by the manufacturer, GESTRA AG.
■
■
Only replace faulty equipment with identical equipment from GESTRA AG.
Starting, operation and testing