Bringing into service
Changing the baud rate
Set the same baud rate for all bus participants.
Pay attention to the setting instructions on page 39 ff. and proceed as follows:
1.
Select the parameter “
bd.rt
”.
2.
Press and hold the rotary knob until the current baud rate flashes on the display.
3.
Set the desired baud rate (50 kBit/s or 250 kBit/s).
4.
Save your set value by pressing the rotary knob for approx. 1 second.
5.
After you have successfully changed the baud rate, restart the entire system.
Changing the limiter ID
To set the limiter ID, please also read the instructions in the Installation & Operating Manual of
the URS 60 / URS 61 safety control unit.
Pay attention to the setting instructions on page 39 ff. and proceed as follows:
1.
Select the parameter “
Id
”.
2.
Press and hold the rotary knob until the current limiter ID flashes on the display.
3.
Set the desired ID (0001 to 0008).
4.
Save your set value by pressing the rotary knob for approx. 1 second.
5.
After you have successfully changed the limiter ID, restart the entire system.
Manually initiating a display test
Pay attention to the setting instructions on page 39 ff. and proceed as follows:
1.
Select the parameter “
diSP
”.
2.
Press and hold the rotary knob until the display test starts by showing “
....
”.
3.
The following numbers run across the display from right to left:
“...., 1, 2, 3, 4, 5, 6, 7, 8, 9, ....”
4.
Check that all numbers are displayed correctly.
The display test runs automatically until it has finished, and cannot be interrupted.
5.
The display test ends automatically with the message “
donE
”.
Replacing faulty equipment
Faulty equipment jeopardises system safety.
■
■
If numbers or decimal points are displayed incorrectly or not at all, you must replace the
level electrode with an identical one from GESTRA AG.