48
NRG 1x-60 - Installation & Operating Manual -
819681-00
System malfunctions
Indication of system malfunctions using fault codes
Fig. 23
Fault code display
Fault code
Internal
designation
Possible faults
Remedy
E.008
Ch1Ch2DiffErr
EMC or
internal error
Check the installation location
Replace the level electrode
E.009
CH2RM:RKErr
Contamination or loss of
insulation
Remove, check and clean the level electrode
E.010
CH2RM+RKErr
EMC or
measuring voltage error
In pressurised hot-water plants, reduce the
conductivity
E.011
CH2RangeErr
Ch2 Out of Range
Check the wiring
Replace the level electrode
E.012
CH1RM:RKErr
Contamination or loss of
insulation
Remove, check and clean the level electrode
E.013
CH1RM+RKErr
EMC or
measuring voltage error
In pressurised hot-water plants, reduce the
conductivity
E.014
Ch1RangeErr
Ch1 Out of Range
Check the wiring
Replace the level electrode
E.015
DutyErr
EMC error or
measuring frequency faulty
Check the installation location
Replace the level electrode
E.016
FreqErr
EMC error or
measuring frequency faulty
Check the installation location
Replace the level electrode
E.017
MWChErr
Measured value test
function fails
Check the wiring
Replace the level electrode
E.018
PWMErr
EMC error or
external voltages
Check the installation location
Replace the level electrode
OK
!
+
-
1
1
Display of actual value/fault code/limit value, green, 4 digits