NRG 1x-60 - Installation & Operating Manual -
819681-00
Starting, operation and testing
Relationship between equipment status, display and alarm LEDs:
Start
Switch on
supply voltage
LED test, all LEDs light up
Display:
S-xx = software version
t-01 = equipment type NRG
1x-60
The system is started and tested.
The LEDs and display are tested.
Operation
Level electrode
immersed
Display:
o.P.E.r.
LED 2
:
Operating LED lights up green
Abbreviation of “operational”
Level electrode
not immersed
Display:
LO.LE
LED 1
:
Alarm LED lights up red
Display LO.LE (LOW LEVEL) and triggering of alarm.
After the time delay has elapsed, the URS 60 / URS
61 safety control unit opens the output contacts.
LED 2
:
Operating LED is OFF
Alarm
Behaviour in the event of a malfunction (fault code display)
On the occurrence of a fault
Display:
e.g. E.008
LED 1
:
Alarm LED lights up red
A fault code is permanently displayed,
fault codes see page 48
There is an active malfunction
LED 2:
Operating LED is OFF
A fault is present
■
■
The malfunction or error state is transferred to the URS 60 / URS 61 safety control unit via CAN data telegram.
■
■
The malfunction causes this unit to execute an undelayed safety shutoff.
■
■
The affected signal output is activated.
■
■
The URS 60 / URS 61 safety control unit does not automatically lock the safety contacts.
Electrode alarms and faults cannot be acknowledged.
When the alarm or malfunction is cancelled the display also goes blank, and the URS 60 /
URS 61 safety control unit closes the safety contacts and deactivates the relevant signal
outputs once more.
See the following page for more information and tables.