![Geotech ORS SITEPRO 2000 Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/geotech/ors-sitepro-2000/ors-sitepro-2000_installation-and-operation-manual_2215571049.webp)
48
Interlock Communication Bus
Type:
RS-485
Capacity:
Supports up to 16 ORS Sitepro™ panels over maximum distance of 3000’ (1000m) using standard 24
AWG 2-conductor twisted shielded pair wire (Belden #9841)
Communications:
Standard 9 pin
RS-232
serial port 300-2400
baud
for data logging (use of special ORS Cable
Assembly PN2390078 is required for local access)*
Certification/Approvals (Pending)
Factory Mutual entity approval on
Intrinsically safe
inputs
*Hardware for enhanced features built into every panel. Features become operational when panel is equipped with
telemonitoring or is networked to a telemonitor equipped ORS Sitepro™ panel.