31
The settings of dip switches 3-6 are determined by using the tables below. Use Table 1 for Master panels and Table 2 for
Slave panels.
If the panel is to be configured as a Master, set dip switch 2 to ON and set dip switches 3-6 to indicate the total number of
Slaves in the
network
(maximum of 15). Table 1 provides dip switch settings for each of the possible numbers of Slaves
in the
network
.
If the panel is to be configured as a Slave, set dip switch 2 to OFF and set dip switches 3-6 to indicate the
address
of the
panel on the network. Use Table 2 to determine the settings of dip switches 3-6 on Slave panels.
MASTER PANELS
Settings for Dip Switches 3-6
Number of Slave
Panels in Network
6
5
4
3
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
9
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
Table - 1
SLAVE PANELS
Settings for Dip Switches 3-6
Number of Slave
Panels in Network
6
5
4
3
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
9
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
Table –2
In Example #1 the controller address switch settings indicate that the panel is a Master and that there are 12 Slave panels
in the
network.
Start at the lowest address (1) and work up (top to bottom in Table 2 with each Slave panel
configured.