Figure 9
Before wiring an older ORS probe to the ORS SITEPRO™ panel, it will be necessary to cut the connector from the probe
cable. After wiring the probe to the panel as shown in figure 9 (above), attach a jumper wire from terminal #5 on TB2 (red
wire) to any of the +5VDC I.S. terminals on TB1.
Wire Sump Probe & Pressure Switches
When the ORS SITEPRO™ is being used to control an air stripper blower and a transfer pump, the ON/OFF cycling of the
pump is controlled by a sump level probe mounted in the air stripper sump. The probe also has a HI-OVERRIDE sensor
that can shut off an optional feed pump if the water level in the air stripper sump rises too high and threatens to flood the
blower.
If your ORS SITEPRO™ 2000 Blower/Pump Control Panel is being used with an ORS LO-PRO™ II Air Stripper, the sump
probe and the pressure switches are pre-wired into a junction box as shown in figure 10. Wire from the junction box to
TB1 and TB2 inside the ORS SITEPRO™ panel as shown in figure 10.
Conductivity actuated probes can be used only with the addition of a relay. Call
Geotech for further information.