Special notice is to be given to the 8A threshold breaking capacity; exceeding this limit will
cause the SS4 fuse to break leaving all connected devices without electricity.
Note:
Due to errors that may cause the switched off power outlet to remain on
it is necessary to conduct the following: Before connecting any power
consuming devices with the SITESWITCH 4 or working on any power
consuming devices already connected to the SITESWTICH 4, make sure
that the SITESWITCH 4 is not connected to the power supply by pulling
its power cable out of the power socket.
Use the provided mounting irons to fix the SS4 into a 19“ rack. Place the SS4 so that the front
panel of the SS4 can be securely s
crewed onto the 19“ rack housing while insuring also that
the power cables can be connected from behind as well.
As soon as all of the power consuming devices are connected to the SS4, the IEC 16 power
supply cable can be connected. Upon establishing power
to the SS4, the green „POWER„ LED
will light up, and the 4 „Power Socket Status LED“ one for each of the sockets should be unlit.
This means that none of the sockets are being provided with power thus cutting the connected
devices from the power supply.
The CS121 establishes a user interface for the SS4 for which the user has the option of using
either UPSMON, Webbrowser, UNMS or an SNMP-Program. All communications take place
either through a modem or network connection. Detailed information is covered in section 7.7.9
AUX and SS4 Settings.
7.1.4
SS4 - Technical data
Inputvoltage:
230V AC +/- 5%
Max. Power Input:
16A
Max. Power Output per socket:
8A (Load at cos phi 1)
Dimensions
260x180x60mm (BxTxH), with 19” : 1,5U
Operating temperature:
0-40°C/rel.Humidity0-95% non condensating
7.2
Sensor SM_T_COM
The SM_T_COM is a temperature sensor for the use with a GENEREX CS121. It has a range
from -25° - 100° Celsisus (-13°
–212° Fahrenheit) and comes with a 1.8 meter cable for
connecting to the CS121 COM2 port. The SM_T_COM is designed for monitoring and
management of 19"- racks, UPS rooms, server and data center rooms and for industrial
applications. Simple Plug' n Play connections insure that the sensor can be easily and safely
installed.
Figure 97:
The Sensor SM_T_COM