49
much higher alarm entry log level than would otherwise be the case if only UPS protocol
defined alarms were being recorded. For explanation, the following illustrates typical log file
entries made by the UPS:
The CS121 logs the time after a new start up:
01/17/2007,16:21:45, Synchronized with timeserver 192.53.103.103. OK
This indicates a successful synchronization with the timeserver.
01/17/2007,16:23:39, UPSMAN <UPS model> has started
UPS communication functions and device is in normal operation mode. This is the standard
entry after every successful reboot of a CS121.
(The following entries result only from user defined settings as with the CS121
ADMINSTRATOR EMAIL Settings.)
01/17/2007,16:28:39, MAIL: subject "CS121 Event 4" successfully sent.
All “EVENT X” designated alarms are viewable in the EVENT list of the web browser. EVENT 4
for this particular UPS is the EVENT "UPSMAN started"
– This means that an Email was sent
with the text "UPSMAN started" which acts to confirm the log entry of 08:06:50 as Email.
01/17/2007,16:28:47, MAIL: subject "CS121 Event 16" successfully sent
In this case, the Scheduler has been activated and is ready for operations. In this case, the
scheduler is set to conduct a "Selftest" which it in turn relays per email to the designated
CS121 ADMIN.
01/17/2007,16:28:47,MAIL: subject "CS121 Event 26" successfully sent
01/17/2007,16:29:03,MAIL: subject "CS121 Event 27" successfully sent
01/17/2007,16:29:28,MAIL: subject "CS121 Event 28" successfully sent
01/17/2007,16:30:46,MAIL: subject "CS121 Event 29" successfully sent
These are 4 Emails indicating the status of the AUX Ports (Auxiliary connection for external
alarms), which are set to give notification of the status signal LOW. Since the AUX Status can
only be set to High or Low and given that the CS121 in itself cannot distinguish the device, an
alarm email will be sent by the CS121 to the designated ADMIN at startup per default with the
startup status of each connected alarm. In this case, it is up to the administrator to determine if
the emails indicate an actual alarm or not.
01/17/2007,16:34:48,MAIL: subject "CS121 Event 38" successfully sent
01/17/2007,16:35:12,MAIL: subject "CS121 Event 39" successfully sent
01/17/2007,16:35:16,MAIL: subject "CS121 Event 40" successfully sent
01/17/2007,16:35:28,MAIL: subject "CS121 Event 41" successfully sent
01/17/2007,16:35:33,MAIL: subject "CS121 Event 42" successfully sent
01/17/2007,16:35:40,MAIL: subject "CS121 Event 43" successfully sent
01/17/2007,16:35:51,MAIL: subject "CS121 Event 44" successfully sent
01/17/2007,16:35:57,MAIL: subject "CS121 Event 45" successfully sent
These are 8 Emails sending information about analogue sensors (temperature, humidity and
the like) that are connected to a SENSORMANAGER, indicating that all controlled values are
within tolerance levels - or that no sensor is connected to the device or connection port.
01/17/2007,16:36:30,MAIL: subject "CS121 Event 54" successfully sent
01/17/2007,16:36:41,MAIL: subject "CS121 Event 55" successfully sent
01/17/2007,16:36:48,MAIL: subject "CS121 Event 56" successfully sent
01/17/2007,16:36:57,MAIL: subject "CS121 Event 57" successfully sent
These 4 Emails indicate that the digital sensors (for airconditioning, fire alarms and the like) of
the SENSORMANAGER, are either in the normal state or that no sensor is connected.
01/17/2007,17:41:12,MAIL: subject "CS121 Event 62" successfully sent
01/17/2007,17:41:36,MAIL: subject "CS121 Event 63" successfully sent
01/17/2007,17:43:23,MAIL: subject "CS121 Event 64" successfully sent
01/17/2007,17:44:01,MAIL: subject "CS121 Event 65" successfully sent