15
You can execute a Terminal configuration via the serial interface (CS121 device types with a
COM2 port only) with the CS121 configuration cable (optional, not included). This
configuration-mode allows you to make the basic settings for the network connectivity and for
the configuration of the event and alarm settings.
3.1.1
... via LAN
Connect the CS121 with RJ45 cable (not included) to your LAN.
3.1.2
... via serial port
The CS121 contains two serial ports (not BL and BSC-versions), COM1 provides the connection to the
UPS and COM2 is used for the configuration of the SNMP adapter.
Configuration cable
(not included):
With the configuration cable you could connect the serial port (COM2) of the CS121 and the serial port
of a workstation with terminal software. It is sufficient to use a Dumb-Terminal or Terminal emulation
program, such as e. g. Microsoft-HyperTerminal. Please ensure during the configuration of the CS121,
that the DIP switches are into position OFF.
CS121 MINI/CS121 R_II:
It is required, that the DIP Switch 2 remains in position OFF, otherwise the device will not start (valid
for CS121Minislot/CS121R_II built 2008- 2010 from serial number 0123M-0001 to 0123M-1135).
3.2
Verifying the CS121 Connectivity
After the CS121 is connected to the UPS and to the workstation via serial port or via LAN, please verify
the connectivity before you start to configure the CS121. The setup system can be checked before and
after a configuration using the following 3 steps:
UPS Status Displays (LEDs)
During the boot procedure, the red LED is on, whereas the green LED is off, please take a look into
chapter 1.6 for the complete signaling.
After five to ten seconds after the boot-process, the green LED flashes rapidly; this indicates that the
SNMP-adapter is trying to start the communication. The adapter will indicate its communication
accessibility with random green LED flashes.
Network status LEDs
The LEDs, integrated into the LAN-Connector (RJ45-), will signal a connection to the network with
green and with yellow network connectivity.
CS121 Ping Echo
Perform a PING command from the SNMP station or from another workstation in your network.
If you do not get a response, check the CS121 network connection and IP address. The IP address of
the adapter is set to 10.10.10.10, if DIP Switch 1 is in position OFF (configuration mode).
Note:
The different response rates during the ping process do not correspond
to an error. The CS121 does not answer every ping signal at the same
time, due to different sized UPS protocols. If UPS protocols are of
extensive size a temporary timeout can occur. A permanent timeout
however is an error.