42
Please note that the CS121 uses the standard MIB, which is included in most SNMP software
already. This MIB is called UPSMIB and corresponds with the Standard RFC1628. In most
cases compiling of the MIB is not required as it can be found under:
iso.org.dod.internet.mgmt.mib2.upsMIB
Please check your MIB directory before compiling the RFC1628!
Configure the NMS
Set/compile the device MIB, if there is no standard UPS MIB RFC 1628 (CS121 only!)
Add the SNMP adapter object to the management map and configuration of the events (e.g.
message to the operator)
Ping the SNMP adapter
Due to the different compilation procedures of the SNMP software products, it is not possible
to explain the general procedures in greater detail. The compilation of a MIB file is explained in
the general SNMP software manuals. Please contact the support, if you cannot resolve errors
using this manual.
After the compilation the UPS software can be polled via a MIB browser and data can be read.
Please choose the corresponding MIB variable or string of MIB variable and set the destination
address TCP/IP of the adapter. The adapter will answer with the UPS data.
Alternatively the Windows UPSMON, JAVAMON or the UPS SNMP WATCH of the DataWatch
Pro Software can be used. The UPS data will then be displayed graphically and internal UPS
information, which are only useful to the technical support, will be hidden. In addition to this,
the UPS SNMP WATCH is able to manage groups of UPS devices, in order to manage parallel
redundant UPS systems.
As an optional add-on for the HP OpenView software, a snap-in may be ordered for
UPSMAN/CS121.
Note:
SNMP response changed: Now only those SNMP requests are answered,
which are present at this UPS or other device. Missing data does no longer cause a return
value "0" or "-1". An SNMP Walk will now no longer return any OIDs, which are not supported
by this UPS.
4.2.15
COM2 & AUX
4.2.15.1
COM2
This menu takes the user into the submenus for the general settings of the COM2 and AUX
connection ports of the CS121-adapter.