UPS Status
EverExceed
Hex-Value
Dec-Value
Description
UPS_SB_BYPASS_MODE
0x0001
1
Bypass mode
UPS_SB_OUTPUT_ACT
0x0004
4
Output active
UPS_SB_OUTPUT_HIGH
0x0100
256
Overload
UPS_SB_UPS_FAILED
0x2000
8192
General alarm
Section Gamatronic DC System
100
U 3 / 4 TEMPDEG
Temperature in Degrees
1
101
U 3 / 4 INVOLT0
AC Input Voltage Phase 1
1
102
U 3 / 4 OUTPUT_VOLT0
DC Output Voltage
1
103
U 3 / 4 EX_OUT_CURR0
Total Output Current
1
104
U 3 / 4 EX_OUT_WATT0
Output Power in Watt
1
105
U 3 / 4 BATTVOLT
Battery Voltage
1
106
U 3 / 4 EX_BATT_CURRPOS
Battery Current
1
107
U 3 / 4 EX_NOM_VOLT
Nominal Voltage
1
108
U 3 / 4 EX_NOM_CURR
Nominal Current
1
109
U 3 / 4 STATUS
GENEREX UPS Status (see below)
1
110
U 3 / 4 (EX_EXTSTATUS & 0xffff0000)>>16 Bytes 98-99 (Device Status)
1
111
U 3 / 4 EX_EXTSTATUS & 0xffff
Bytes 100-101 (Device Status)
1
112
U 3 / 4 (STATUS&0x02)>>2
Output active,
1 = on, 0 = off
1
113
U 3 / 4 (STATUS&0x20)>>5
Overtemperature,
1 = on, 0 = off
1
114
U 3 / 4 (STATUS&0x40)>>6
Test active,
1 = on, 0 = off
1
115
U 3 / 4 (STATUS&0x100)>>8
Overload,
1 = on, 0 = off
1
116
U 3 / 4 (STATUS&0x2000)>>13
General alarm,
1 = on, 0 = off
1
UPS Status
Gamatronic DC System
Hex-Value
Dec-Value
Description
UPS_SB_OUTPUT_ACT
0x0004
4
Output active
UPS_SB_OVER_TEMP
0x0020
32
Overtemperature
UPS_SB_TEST_ACT
0x0040
64
Test active
UPS_SB_OUTPUT_HIGH
0x0100
256
Overload
UPS_SB_UPS_FAILED
0x2000
8192
General alarm
Other OEM’s
->See
OEM MODBUS
documentation
E.6.
UPSMAN Status Bytes - Standard Device Status Bits