17
As soon as the network-LED is flashing, add a TCP/IP route on your computer for IP-
address 10.10.10.10. This is done via a call from your command line e.g. "route add
10.10.10.10 <your computers IP address>“. See also route -? for more help of route syntax.
Test if you can pin
g the device now: Enter command „ping 10.10.10.10“ and check if there is
any response. Now you can connect with any Telnet or HTTP-software and continue with the
configuration.
3.3.3
Using HTTP/Webbrowser
Attention!
Please finish all configuration menus via “Apply”button. After you
finished your whole confguration, please note, that it is reqzuired to execute the “Save, Exit &
Reboot” function via CS121 menu “Save Configuration”.
The entire configuration can be done via Webbrowser. Please use the default IP-address
10.10.10.10 and the TELNET password
(def
ault: “cs121-snmp”)
. The username is always
“admin”.
Please do never close the web-browser or telnet window during saving process! If you close
the configuration window too early, you might destroy the configu
ration file “upsman.cfg”.
Please note, that the reboot process could last up to 3 minutes.
For the configuration using the webbrowser please observe the following:
We recommend the use of Microsoft Internet Explorer 6.x (or higher) or Mozilla 1.3x. Please
note, that Java scripting has to be activated. Using Internet Explorer, the corresponding
settings have to be made under “Internet options” - “security”.
We also recommend never to use the history function of the browser, as this may lead to
multiple transfer of commands (e.g. delete event jobs) to the adapter.
Upon entering a HTTP-configuration session, the user is required to enter a username,
”admin”, in addition to the password ”cs121-snmp”.
Figure 5:
HTTP - Administrator login
Note:
If the HTTP-method does not seem to be available, check to see
whether or not the red LED UPS Status glows.
Call Configuration, “UPS Model & System” and choose your UPS Model from the drop
down list. Further configurations like Power, baud rate, cable type etc. were made
automatically (ensure your Browser has enabled JavaScript) and do not need to be set. We
strongly recommend to keep the default settings for this UPS unless you have instructions
from the UPS maker.