Switch UPS Outlet:
This is a function to switch of the UPS outlets (not provided of every
UPS).
Switch AUX port:
In general the AUX port is used for additional contacts, which can be
configured as in- or output (e. g.: as input for alarm contacts of an air conditioner or as an
output to switch a connector). If the contacts will be configured as inputs, they are able to be
used as event in the “Event Settings”. Additionally you can establish jobs, if they are
configured as outputs. The menu “Switch AUX port” is for outputs only. You cannot switch
inputs!
RCCMD Shutdown:
Here, IP-addresses from computers with RCCMD connection (receivers)
in the network can be entered. The CS121-adapter can then initiate a multi-server shutdown.
The timing for such a shutdown procedure depends on the configured down time of the
adapter (default: time of the remaining capacity of battery in min., during a long power fail.) or
on a countdown timer. Extended CS121-adapters can also use more events (e.g. battery low,
battery defect, communication lost etc.) as RCCMD signals. Please contact your UPS dealer
for more information.
RCCMD Message:
With this job the user can combine and configure a text message with
RCCMD event. Text messages can be sent to RCCMD receivers. This makes it possible to
send text messages via RCCMD (version 2 or higher) to a Windows 2000 server or a Unix
computer, using the “NET SEND” or the respective “WALL” method. The problem with notifying
network users on different operating systems is therefore solved.
RCCMD Command:
This RCCMD signal will cause any RCCMD receiver (e.g. another
CS121, RCCMD client or SITEMANAGER, SITESWITCH4) to execute a command or
program, e. g.: to start a program at a remote work station.
Native UPS Command:
(for very experienced users only) This is a function to execute UPS
own commands. Assumption: The user knows the “Command IDs” and the proper parameter.
These commands require additional parameter. If you want to use these kind of commands,
just contact your UPS dealer.
(De-) Activate Event:
This is a function to switch off appointed events/alarms.
Send WOL:
WOL stands for “Wake on LAN”. This function uses data packages to prompt
other computers in a local network to start-
up. Please use this function in the event “UPSMAN
started” to wake up computers which have been shut downed previously after an extended
power outage, which cause the CS121 or UPS to switch off completely. Additional you may
add this WOL signal to the EVENT “Power restored”. Advice: Not every network cards are
providing this function or are password protected. Activate this function into the BIOS settings
of the motherboard.
Send Periodic Email:
This is a function to send the log files via email periodically (from
firmware 4.xx and higher).
4.2.19
Save Configuration / Reboot
If you are satisfied with your configuration select “Save, Exit & Reboot” and wait until the
adapter informs you about the reboot-process. Do NOT close your web-browser!
4.3
Reading the Logfiles
The CS121-Alarmlog contains the alarm protocol of events that were designated as alarms in
the Event/Settings-section and include the user defined alarm settings of the CS121
configuration as well as the events that are designated as alarms in the UPS native protocol.
These entries include such things as CS121 Admin defined email notifications which lead to a