125
141 U 3 / 4
Input Bad Condition
Input Bad Condition
1
142 U 3 / 4
Output Bad Condition
Output Bad Condition
1
143 U 3 / 4
Bypass Not Available
Bypass Not Available
1
144 U 3 / 4
Low Battery Shutdown
Low Battery Shutdown
1
145 U 3 / 4
System off
System off
1
146 U 3 / 4
System Shutdown
System Shutdown
1
147 U 3 / 4
Charger Failure
Charger Failure
1
148 U 3 / 4
Manual Restart Required
Manual Restart Required
1
149 U 3 / 4
Output Circuit Breaker
Open
Output Circuit Breaker Open
1
150 U 3 / 4
Remote Emergency Power
off
Remote Emergency Power off
1
151 U 3 / 4
Shutdown imminent
Shutdown imminent
1
Section OEM Netminder for all other types
Address Type Function Name
Description
Length
100
U
3/4
INVOLT
Input Voltage (l1-n)
1
101
U
3/4
INVOLT
Input Voltage (l2-n)
1
102
U
3/4
INVOLT
Input Voltage (l1-l2)
1
103
U
3/4
OUTPUTVOLT
Output Voltage (l1-n)
1
104
U
3/4
OUTPUTVOLT
Output Voltage (l2-n)
1
105
U
3/4
OUTPUTVOLT
Output Voltage /(l1-l2)
1
106
U
3/4
OUTPUTCURR
Output Current (l1-n)
1
107
U
3/4
OUTPUTCURR
Output Current (l2-n)
1
108
U
3/4
OUTPUTWAT
Output Watts (l1-n)
1
109
U
3/4
OUTPUTWAT
Output Watts (l2-n)
1
110
U
3/4
OUTPUTWAT
Output Watts (l1-l2)
1
111
U
3/4
OUTPUTWATTOT
Output watts (total)
1
112
U
3/4
OUTPUTVA
Output VA (l1-n)
1
113
U
3/4
OUTPUTVA
Output VA (l2-n)
1
114
U
3/4
OUTPUTVA
Output VA (l1-l2)
1
115
U
3/4
OUTPUTVATOT
Output VA (total)
1
116
U
3/4
OUTPUTLOAD
Output Load (l1-n)
1
117
U
3/4
OUTPUTLOAD
Output Load (l2-n)
1
118
U
3/4
OUTPUTFREQ
Output Frequency
1
119
U
3/4
BATTVOLT
Battery Voltage
1
120
U
3/4
PERCBATT
Percentage Battery
1
121
U
3/4
DCCHARGECURR
DC Charging Current
1