Model S4000CH
6
construction; therefore, they shall only be used with the enclosure type and where the surface
temperature, at the point of mounting, is as detailed below:
Cement
Ambient Range
Enclosure Type
2850FT Cat 11,
2762 Cat 17
-40°C to +70°C
Enclosures that are certified by a notified body and
satisfy the requirements of the current edition of EN
60079-1 or EN 60079-7 and European Directive
94/9/EC.
2850FT Cat 11
-40°C to +120°C
Enclosures that are certified by a notified body and
satisfy the requirements of the current edition of EN
60079-7 and European Directive 94/9/EC.
2762 Cat 17
-40°C to +180°C
Enclosures that are certified by a notified body and
satisfy the requirements of the current edition of EN
60079-7 and European Directive 94/9/EC.
The Universal Gas Sensor (11159-XX), when tested in accordance with clause 15.4.2.1 of EN
60079-1, produced a maximum surface rise of 26.3 K. This value should be considered when
the component is incorporated into equipment.
The Universal Gas Sensor (11159-XX), utilizing Types 2850FT Cat 11 and 2762 Cat 17
cement shall only be fitted to enclosures having a maximum reference pressure of 9.6 bar.
1.3 System Integrity Verification
Commissioning Safety Systems
Before power up, verify wiring, terminal connections and stability of mounting for all integral
safety equipment including, but not limited to:
Power supplies
Control modules
Field detection devices
Signaling / output devices
Accessories connected to field and signaling devices
Remote Gas Calibrator (RGC) / Automatic Remote Gas Calibrator (ARGC)
After the initial application of power (and any factory specified warm-up period) to the safety
system, verify that all signal outputs, to and from devices and modules, are within the
manufacturer’s specifications. Initial testing should be performed per the manufacturer’s
recommendations and instructions.
Proper system operation should be verified by performing a full, functional test of all
component devices of the safety system, ensuring that the proper levels of alarming occur.
Fault/Malfunction circuit operation should be verified.