Model S4000CH
25
After a few seconds, the current Alarm relay set point is displayed. Apply and remove the
magnet until the desired set point is displayed. Once the desired set point value is shown,
wait 3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to return to the
next level of the Setup menu. When “
Fi
” is displayed again, apply and remove the magnet
to return to normal operation.
The default Alarm relay settings are: latching, de-energized, 60% LEL set point.
NOTE:
The Alarm relay set point cannot be set lower than the Warning Relay set point, or
higher than 60% LEL.
3.11.5 Modbus Channel 1 Settings
To change the Modbus Channel 1 settings of the S4000CH, apply the magnet to the GM
logo on the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the
unit into Setup Mode. After a few seconds “
CH1
” will be displayed. Apply and remove the
magnet to change the Modbus Channel 1 settings.
First, the current Baud Rate Modbus Channel 1 is displayed. If another baud rate is to be
selected, apply and remove the magnet until the desired baud rate is displayed. The
choices are: 19.2k baud “
19.2
”, 9600 baud “
96
”, 4800 baud “
48
”, or 2400 baud “
24
”.
After a few seconds, the current Data Format for Modbus Channel 1 is displayed. If
another data format is to be selected, apply and remove the magnet until the desired data
format is displayed. The choices are: 8-N-1 “
8n1
”, 8-N-2 “
8n2
”, 8-E-1 “
8E1
”, or 8-O-1
“
8O1
”.
After a few seconds, the current address for Modbus Channel 1 is displayed. Apply and
remove the magnet until the desired address is displayed. Once the desired address is
displayed, wait 3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to
return to the next level of the Setup menu. When “
Fi
” is displayed again, apply and
remove the magnet to return to normal operation.
Default settings for Channel 1 are:
address 1, 19.2k baud, 8-N-1.
NOTE:
The address can be adjusted from 1 - 247. Channel 1 and Channel 2 addresses
may be the same.
3.11.6 Modbus Channel 2 Settings
To change the Modbus Channel 2 Settings of the S4000CH, apply the magnet to the GM
logo on the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the
unit into Setup Mode. After a few seconds “
CH2
” will be displayed. Apply and remove the
magnet to change the Modbus Channel 2 settings.
First, the current Baud Rate Modbus Channel 2 is displayed. If another baud rate is to be
selected, apply and remove the magnet until the desired baud rate is displayed. The
choices are: 19.2 kbaud “
19.2
”, 9600 baud “
96
”, 4800 baud “
48
”, or 2400 baud “
24
”.
After a few seconds, the current Data Format for Modbus Channel 2 is displayed. If
another data format is to be selected, apply and remove the magnet until the desired data
format is displayed. The choices are: 8-N-1 “
8n1
”, 8-N-2 “
8n2
”, 8-E-1 “
8E1
”, or 8-O-1
“
8O1
”.