Model S4000CH
4
NOTE:
Power must remain disconnected until all other wiring connections have been made.
The maximum distance between the S4000CH and the power supply is 3430 feet or 1040
meters (each cable run should be as short as possible). See Section 7.3.4 for cable length
specifications.
C24 VDC to TB2, position 9. Connect the ground or common to TB2, position 8.
To connect the analog signal, please refer to Section 3.5.4.
General Monitors recommends that the S4000CH Intelligent Sensor be calibrated one hour
after start-up, and that the calibration be checked at least every ninety (90) days to ensure
system integrity.
The instrument is now ready to operate. Please consult the manual for more information on the
instrument’s many features.
NOTE
: If you have any problems in the set-up or testing of the detector, please refer to the
“Troubleshooting Section”, or call the factory direct. See Section 5.2.