Model S4000CH
12
3.4 Mounting and Wiring
WARNING:
Unused cable entry holes must be sealed with a suitably certified ATEX or
IECEx explosion-proof stopping plug. Red caps supplied by General Monitors
are for dust protection only, and must not be left on the unit when installed.
WARNING: Conduits must be sealed within 18 inches of the enclosure.
The outline and mounting dimensions for the S4000CH (Figure 10) should be used when
making installation determinations. A complete list of the mechanical specifications can be
found in Section 7.3.2.
To prevent possible corrosion due to moisture or condensation, it is recommended that the
conduit connected to the S4000CH housing contain a drain loop.
NOTE:
For ATEX and IECEx applications, conduit connections must only be made via
suitably certified ATEX (or IECEx as appropriate) conduit stopping boxes.
Information on Class I Division 1 and Zone 1 wiring methods can be found in the NEC and
CEC.
WARNING:
Acetic acid will cause damage to metal components, metal hardware, ceramic
IC’s, etc. If damage results from the use of a sealant that outgases acetic acid
(RTV silicone), the warranty will be void.
Figure 10: Outline and Mounting Dimensions in inches