Parameter
Function
Type
Scale
Access
Register
Address
Master
I/O
Address
Ch2 Function
Code Errors
Total # of Function Code
Errors
Value
16-Bit
R
0072
40115
Ch2 Starting
Addr Errors
Total # of Starting Address
Errors
Value
16-Bit
R
0073
40116
Ch2 No of
Register Errors
Total # of Register Errors
Value
16-Bit
R
0074
40117
Ch2
CRC errors
Value
16-Bit
R
0075
40118
Ch2
CRC errors
Value
16-Bit
R
0076
40119
Ch2 Parity Errors Total parity errors
Value
16-Bit
R
0077
40120
Ch2 Overrun
Errors
Total overrun errors
Value
16-Bit
R
0078
40121
Ch2 Framing
Errors
Total Framing errors
Value
16-Bit
R
0079
40122
Ch2 Software
Errors
Total Ch 2 Software request
errors
Value
16-Bit
R
007A
40123
Not used
40124
Ch2 Clear Errors
Ch2 Clear Hardware errors
Bit
0
R/W
007C
40125
Ch2 Clear Errors
Ch2 Clear Software errors
Bit
0
R/W
007D
40126
Not used
007E
40127
6.8 S4000CH Command Register Details
6.8.1 Analog
(00h)
A read returns a value, which is proportional to the 0-20 mA output current. The current is
based on a 16-bit value. The scaling is 0 - 65535 decimal which corresponds to 0 - 21.7 mA.
6.8.2 Mode
(01h)
A read returns the present mode of the S4000CH.
A write command changes the mode to the requested mode. A data value of 08 will start
calibration mode if the unit is in the run mode. It also will go from cal check to cal mode.
A write command with the data value of 04 will put the unit in Cal Check Mode if there are no
errors or alarms.
Exception: Returns an Exception Code 01 (illegal function) if an illegal write is requested.
Function
Bit Position
Hex value
Access
Calibration Complete
7 MSB
80
Read
Spanning 6
40
Read
Zero Complete, Waiting for Gas 5
20
Read
Zeroing 4
10
Read
Calibration Mode
3
08
Read/Write
Calibration Check Mode
2
04
Read/Write
Run Mode
1
02
Read
Startup Mode
0 LSB
01
Read
Содержание S4000CH