Model S4000CH
24
3.11.2 Calibration Level
NOTE:
Refer to Section 3.14.1 for the calibration procedure.
To adjust the calibration level of the S4000CH, apply the magnet to the GM logo on the
cover of the unit, until “
SE
” is displayed, then remove the magnet. This puts the unit into
Setup Mode. After a few seconds “
cL
” will be displayed. Apply and remove the magnet to
adjust the calibration level. The current calibration level will be displayed. To change the
calibration level, apply and remove the magnet repeatedly, until the desired level is
displayed. Holding the magnet in place will cause the display to advance rapidly after a
few seconds. Once the desired value is displayed, wait 3 seconds and “
Fi
” will be
displayed. Apply and remove the magnet to return to the next level of the Setup menu.
When “
Fi
” is displayed again, apply and remove the magnet to return to normal operation.
The default calibration level is 50% LEL
.
3.11.3 Warning Relay Settings
To adjust the Warning Relay Settings of the S4000CH, apply the magnet to the GM logo
on the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the unit
into Setup Mode. After a few seconds “
Lo
” will be displayed. Apply and remove the
magnet to change the Warning or “Low” alarm settings.
First, the Energized/De-Energized state of the relay is shown by either “
En
” or “
dE
” being
displayed, respectively. Apply and remove the magnet until the desired state is displayed.
After a few seconds, the Latching/Non-Latching state of the relay is shown by either “
La
”
or “
nL
”. Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the current Warning relay set point is displayed. Apply and remove
the magnet, until the desired set point is displayed. Once the desired set point value is
displayed, wait 3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to
return to the next level of the Setup menu. When “
Fi
” is displayed again, apply and
remove the magnet, to return to normal operation.
The default Warning Relay Settings are: non-latching, de-energized, 30% LEL set
point.
NOTE:
The Warn relay set point cannot be set higher than the Alarm Relay set point, or
higher than 60% LEL.
3.11.4 Alarm Relay Settings
To adjust the Alarm Relay Settings of the S4000CH, apply the magnet to the GM logo on
the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the unit
into Setup Mode. After a few seconds “
Hi
” will be displayed. Apply and remove the
magnet to change the Alarm or “High” alarm settings.
First, the Energized/De-Energized state of the relay is shown by either “
En
” or “
dE
” being
displayed respectively. Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the Latching/Non-Latching state of the relay is shown by either “
La
”
or “
nL
”. Apply and remove the magnet, until the desired state is displayed.