Troubleshooting / Quick Reference Guide
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
39
Quick Reference Guide
To clear an active alarm, press OFF button and then ENTER button on controller. Then press the AUTO mode button.
If the alarm reoccurs, contact an IASD.
Active Alarm
LED
Problem
Action
Solution
NONE
FLASHING
GREEN
Unit running in AUTO but
no power in house.
Check generator set
MLCB (generator set
disconnect).
Check generator set MLCB (generator set
disconnect). If it is ON, contact an IASD.
HIGH
TEMPERATURE
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Inspect ventilation around generator set,
intake, exhaust, and rear of generator set.
Contact an IASD if no obstructions are
present.
OVERLOAD
REMOVE LOAD
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from the generator set. Put in AUTO and
restart.
RPM SENSE
LOSS
RED
Unit was running and shut
down, attempts to restart.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from the generator set. Put into AUTO and
restart. Contact an IASD if generator set
does not start.
NOT ACTIVATED
NONE
Unit will not start in AUTO
with mains power loss.
Check if screen says
unit not activated.
See Activation section in installation
manual.
NONE
GREEN
Unit will not start in AUTO
with mains power loss.
Check screen for start
delay countdown.
If the startup delay is greater than
expected, contact an IASD to adjust from 2
to 1500 seconds.
LOW OIL
PRESSURE
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Check oil level and add oil as needed.
Contact an IASD if oil level is correct.
RPM SENSE
LOSS
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
MENU option from the MAIN MENU. If
battery condition displays GOOD, contact
an IASD. If control panel displays CHECK
BATTERY, replace the battery.
OVERCRANK
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Verify fuel line shutoff valve is ON. Clear
alarm. Start the unit in MANUAL. If it does
not start, or starts and runs rough, contact
an IASD.
LOW VOLTS
REMOVE LOAD
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from the generator set. Put in AUTO and
restart.
OVERSPEED
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
UNDERVOLTAGE
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
UNDERSPEED
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
STEPPER
OVERCURRENT
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.
WIRING ERROR
RED
Unit will not start in AUTO
with mains power loss.
Check LEDs / screen
for alarms.
Contact an IASD.