![Generac Power Systems G0071450 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/generac-power-systems/g0071450/g0071450_owners-manual_2209512036.webp)
Maintenance
30
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
Maintenance Log
Battery inspection and charge check
Dates Performed:
Oil, oil filter, air filter, and spark plug replacement
Dates Performed:
Valve Adjustment
Dates Performed:
Checking Engine Oil Level
IMPORTANT NOTE: Verify oil level daily when power
outages necessitate running the generator set for
extended periods.
Proceed as follows to check engine oil level:
1.
Verify unit is in OFF mode.
2.
Remove oil dipstick and wipe dry with a clean
cloth.
3.
Completely insert oil dipstick into oil dipstick tube
and remove it.
4.
Observe oil level. Oil level should be at FULL mark
on oil dipstick.
5.
If necessary, remove oil fill cap and add oil to
engine (with oil dipstick removed). Repeat steps 3
and 4 until oil level reaches FULL mark.
6.
When oil level is correct, insert oil dipstick and
tighten oil fill cap.
7.
Perform all steps in “To turn the generator set back
ON” in
Generator Set Enable/Disable Proce-
Engine Oil Requirements
Engine oil should be serviced in accordance with the rec-
ommendations of this manual to maintain product war-
ranty. Maintenance kits consisting of engine oil, oil filter,
air filter, spark plug(s), a shop towel, and a funnel are
available through an IASD.
All Generac oil kits meet minimum American Petroleum
Institute (API) Service Class SJ, SL, or better. Do not use
special additives.
Required Oil
Synthetic SAE 5W-30 for all temperature ranges.
See
.
NOTE:
The unit comes from the factory filled with 5W-30
weight organic oil.
ISO000139
Follow proper shutdown procedure for
cooling if generator is running. Failure to
do so may create a burn hazard.
ISO000210
Skin irritation. Avoid prolonged or repeated
contact with used motor oil. Used motor oil has
been shown to cause skin cancer in laboratory
animals. Thoroughly wash exposed areas with
soap and water. Rubber gloves are
recommended.
ISO000135
Engine damage. Verify proper type and
quantity of oil prior to starting engine.
Failure to do so could result in engine
damage.
Содержание G0071450
Страница 4: ...iv Owner s Manual for 50 Hz Air Cooled Generator Sets...
Страница 16: ...Safety Information 10 Owner s Manual for 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 32: ...Operation 26 Owner s Manual for 50 Hz Air Cooled Generator Sets This page intentionally left blank...
Страница 47: ......