Maintenance
32
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
6.
See
. Verify spark plug gap using a wire
feeler gauge. Replace spark plug(s) if spark plug
gap is out of specification. See
Figure 4-5. Spark Plug Gap Measurement
7.
Install spark plug(s), and tighten to 25 Nm (18.4 ft-
lbs).
8.
Install front access panel.
9.
Perform “To turn the generator set back ON” in
Generator Set Enable/Disable Procedure
Checking and Adjusting Valve
Clearance
Check valve clearance according to the
. Adjust if necessary.
Checking Valve Clearance
NOTE:
The engine must be cool before checking valve
clearance. Adjustment is not needed if valve clearance is
within the dimensions provided in
1.
Perform “To turn the generator set OFF” in
ator Set Enable/Disable Procedure
.
2.
Remove front access panel and intake side panel
as described in
and
.
3.
Turn off generator set fuel supply and disconnect
negative battery cable to avoid accidental start-up.
4.
Remove spark plug wires, and position wires away
from spark plugs.
5.
Remove spark plugs using a 13/16 in socket
wrench (8 kVA units) or a 5/8 in socket wrench
(10–13 kVA).
6.
Remove the four screws attaching one valve cover
using a 10 mm socket wrench. Remove and dis-
card gasket.
7.
Verify piston is at top dead center (TDC) of its com-
pression stroke (both valves closed). To move pis-
ton to TDC, remove intake baffle at the front of the
engine to access flywheel nut. Use a 30 mm socket
(8 kVA) or 36 mm socket (10–13 kVA) to rotate fly-
wheel nut clockwise, which will rotate the crank-
shaft. Watch piston through spark plug hole. The
piston should move up and down. Piston is at TDC
when it is at its highest point of travel.
8.
See
. Verify valve clearance between
rocker arm (E) and valve stem (F) with a feeler
gauge.
Figure 4-6. Check and Adjust Valve Clearance
9.
Repeat steps 6–8 for second cylinder.
10.
Install replacement valve cover gaskets.
11.
Install valve covers.
NOTE:
Start all four screws before tightening, or it will
not be possible to get all screws in place. Verify valve
cover gasket is in place.
12.
Tighten fasteners in a cross pattern, tightening to
6.8 Nm (60
in-lbs
).
13.
Install spark plugs and tighten to 25 Nm (18 ft-lbs).
14.
Attach spark plug wires to spark plugs.
15.
Reconnect negative battery cable and turn on gen-
erator set fuel supply.
16.
Install intake side panel and front access panel.
17.
Perform “To turn the generator set back ON” in
Generator Set Enable/Disable Procedure
000211
ISO000534
Contact an IASD for service assistance.
Proper valve clearance is essential for
prolonging engine life.
002380
C
D
E
F