![Generac Power Systems G0071450 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/generac-power-systems/g0071450/g0071450_owners-manual_2209512028.webp)
Operation
22
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
Setting the Exercise Timer
This generator set is equipped with a configurable exer-
cise timer. There are two settings for the exercise timer:
Day/Time:
Generator set will start and exercise for the
period defined, on the day of the week and at the time of
day specified. During this exercise period, the unit runs
for approximately five minutes and then shuts down.
NOTE:
If Wi-Fi is enabled, the exercise timer will auto-
matically adjust for Daylight Saving Time.
Exercise frequency:
Exercise frequency can be set to
Weekly, Biweekly, or Monthly. If Monthly is selected, day
of the month must be selected from 1-28. Generator set
will exercise on that day each month. Transfer of loads to
the generator output does not occur during the exercise
cycle unless mains power is lost.
NOTE:
The exercise feature will operate only when the
generator set is in AUTO mode, and will not work unless
this procedure is performed. If Wi-Fi is NOT enabled, the
current date/time will need to be reset every time the 12
volt battery is disconnected and then reconnected, and/or
when the fuse is removed.
details exercise information and programming
options for all home standby generator sets.
illustrates the engine speed profile during a typical exercise
cycle.
Figure 3-7. Low Speed Exercise Profile
Emergency Stop
All generator sets are equipped with an emergency stop
device. This device is intended to be used in emergency
circumstances where the generator set must be shut
down immediately to avoid harm. When the emergency
stop button is pressed, the generator set will shut down
and enter into an Alarm condition.
•
This device is not intended to be used as the only
safeguard during maintenance or service opera-
tions. Follow the appropriate procedures in this
manual to correctly disable the generator set
during maintenance and service operations.
•
This device is not intended to be the primary
means of shutting down the generator set. See
generator set shutdown sequence in
for shutdown proce-
dures.
Proceed as follows to reset emergency stop:
1.
Pull out emergency stop button.
2.
Clear alarm by pressing OFF button and then
ENTER button on the control panel.
3.
Generator set is now in OFF mode. Select desired
operating mode (if required).
Operating Modes
Manual
•
Will not transfer to generator set if mains power is
present.
•
Will transfer to generator set if mains power fails
(below 65% of nominal for five consecutive sec-
onds) after warm-up.
•
Will transfer back when mains power returns for 15
consecutive seconds. Engine will continue to run
until removed from MANUAL mode.
Auto
•
Will start and run if mains power fails for five con-
secutive seconds (factory default).
•
Will start an engine warm-up timer (duration varies
when
is enabled).
– Will not transfer if mains power subsequently
returns.
– Will transfer to generator set if mains power is
not present.
•
Will transfer to mains power once mains power
returns (above 80% of nominal) for 15 seconds.
•
Will not transfer to mains power unless mains
power returns. Generator set will shut down if OFF
button is pressed or a shutdown alarm is present.
•
Once mains power is returned, generator set will
shut down after one minute cool-down time.
Table 3-1. Generator Set Exercise Characteristics
Generator set size
8-13 kVA
Low speed exercise
(Quiet-Test™)
1950 rpm
Exercise frequency options
Weekly/Bi-Weekly/Monthly
Exercise time length
5 minutes
2600
2800
3000
3200
3400
3600
3800
>Žǁ^ƉĞĞĚdžĞƌĐŝƐĞWƌŽĮůĞͶϱϬ,njϴͲϭϯŬs'ĞŶĞƌĂƚŽƌƐ
1800
2000
2200
2400
0 sec
5 s
10 s
15 s
20 s
25 s
30 s
35 s
40 s
45 s
1 min
5 min
Exercise Speed (RPM)
Exercise Time
005964